台达可编程控制器(PLC)DVP04AD-SL安装说明pdf,台达可编程控制器(PLC)DVP04AD-SL安装说明:。DVP04AD-SL 模拟量信号输入模块可透过DVPSV/EH2-L 主机程序以指令FROM/TO 来读写数据。模拟量信号输入模块接受来自PLC主机的4 组16 位数字数据,再将数字数据转换为4 点模拟量信号输入(电压或电流皆可)。模块内具有多个CR (Control Register) 寄存器,每个寄存器有16bits。使用者可经由配线选择电压输入或电流输入,电压输入范围 -10V ~ 10VDC (分辨率为312.5uV),电流输入范围-20mA ~ 20mA (分辨率为625nA)。
资源推荐
资源详情
资源评论
DVP-1050130-02
2010
-
06
-
29
50
11
69600
1-A4L1
- 1 -
………………………………………………………………… ENGLISH …………………………………………………………………
Thank you for choosing Delta’s DVP series PLC. The analog input module of
DVP04AD-SL series can read/write the data of analog input module by using
instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module
receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points
analog input signal either in voltage or in current. Users can select input from voltage or
current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5μV). Current
input range is -20mA ~ 20mA (resolution is 625nA).
a This instruction sheet provides only information on the electrical specification,
general functions, installation and wiring. For detailed program design and applicable
instructions, please refer to “DVP-ES2 Operation Manual: Modules”. For details of
the optional peripheral, please refer to the instruction sheet enclosed in the package.
a This is an OPEN TYPE I/O module and therefore should be installed in an enclosure
free of airborne dust, humidity, electric shock and vibration. The enclosure should
prevent non-maintenance staff from operating the device (e.g. key or specific tools
are required for operating the enclosure) in case danger and damage on the device
may occur.
a DO NOT connect the input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power.
Make sure the ground terminal is correctly grounded in order to prevent
electromagnetic interference.
a Tightening torque for I/O terminal block is 1.95 kg-cm (1.7 in-lbs) and please uses
60/75°C copper conductors only.
Product Profile & Dimension
60 [2.362]
33.1 [1.303]
3 [0.118]
90 [3.543]
63.4 [2.496]
DVP-04AD
5
2
3
4
6
7
8
9
5
10
1
[ Figure 1 ]
Unit: mm
[
inch
]
1. I/O module connection port 6. Mounting hole of the I/O module
2. Status indicator
(POWER, RUN and ERROR)
7. I/O module connection port
3. Model name 8. Mounting slot (35mm)
4. I/O terminals 9. I/O module clip
5. Mounting slot clip 10. DC power input
I/O Terminal Layout
DVP04AD-SL (4AI)
I2+V2+FGV1-I1+V1+ V3-
I3+V3+
FGV2- V4-I4+V4+FG FG
CH1 Ch2 Ch3 Ch4
- 2 -
External Wiring
y Active-type
CH1
1M
250
V1+
I1+
VI1-
CH1
CH4
V4+
I4+
VI4-
CH4
*5
*2
AG
0V
24V
DC/DC
+15V
-15V
AG
FE
FE
*3
*4
Voltage input
Current input
Shielded cable*1
Shielded cable*1
Termin al of
power module
System
grounding
Grounding
(100 or less)
Converter
[ Figure 2 ]
1M
1M
250
AG
1M
+
-
U
IN
+
-
U
IN
y Passive-type
CH1
1M
250
V1+
I1+
VI1-
CH1
CH4
V4+
I4+
VI4-
CH4
*5
*2
AG
0V
24V
DC/DC
+15V
-15V
AG
FE
FE
*3
*4
Voltage input
Current input
Shielded cable*1
Shielded cable*1
Terminal of
power module
System
grounding
Grounding
(100 or less)
Converter
[ Figure 3 ]
1M
1M
250
AG
1M
-
+
U
IN
-
+
Note 1: When performing analog input, please isolate other power wirings.
Note 2: When the A/D module is connected to current signals, make sure you short-circuit “V+” and
“I+” terminals.
Note 3: If the noise is too significant, please connect FE to the grounding terminal.
Note 4: Please connect the
terminal on both the power module and A/D module to the system earth
point and ground the system contact or connect it to the cover of power distribution cabinet.
Note 5: If the ripples at the loaded input terminal are too significant that causes noise interference on
the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor.
Electrical Specifications
Analog / Digital module Voltage input Current input
Power supply voltage
24VDC (-15% ~ +20%) / 3.5W
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
Analog input channel 4 channels / each module
Range of analog input ±10V ±5V ±20mA 0 ~ 20mA 4 ~ 20mA
Range of digital
conversion
±32,000 ±32,000 ±32,000 0 ~ 32,000 0 ~ 32,000
- 3 -
Analog / Digital module Voltage input Current input
Hardware Resolution
16 bits 16 bits 16 bits 15 bits 15 bits
Input impedance < 0.5Ω
Overall accuracy
±0.3% when in full scale (25°C, 77°F)
±0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)
Response time 250μs / each channel
Max. output current 1KΩ ~ 2MΩ -
Tolerance carried
impedance
- 0Ω~500Ω
Digital data format 2’s complement of 16 bits, 15 significant bits
Isolation method
Optical coupler isolation between digital circuits and analog circuits.
No isolation among analog channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Series connection to
DVP-PLC MPU
Connectable to the left side of MPU, numbered from 100 to 107
according to the position of module from the closest to farthest to
MPU.
Operation/storage
temperature
Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Control Register
CR# Attrib. Register name Explanation
#0 O R
Model name
Set up by the system:
DVP04AD-SL model code = H’4400
#1 O R
Firmware version
Display the current firmware version in hex.
#2 X R/W
CH1 input mode setting
#3 X R/W
CH2 input mode setting
#4 X R/W
CH3 input mode setting
#5 X R/W
CH4 input mode setting
Input mode: Default = H’0000.
Take CH1 for example:
Mode 0 (H’0000): Voltage input (±10V)
Mode 1 (H’0001): Current input (±20mA)
Mode 2 (H’0002): Current input (0~+20mA)
Mode 3 (H’0003): Current input (+4~+20mA)
Mode 4 (H’0004): Voltage input (±5V)
Mode 5 (H’0005): Voltage input (0V~+5V)
Mode 6 (H’0006): Voltage input (1V~+5V)
Mode -1 (H’FFFF): Channel 1 unavailable
b15 ~ b12 b11 ~ b8 b7 ~ b4 b3 ~ b0
CH4 CH3 CH2 CH1
#6 X R/W
History mode
Only average values are recorded.
Default = H’0000. Take CH1 for example:
K0: Disable (Default). K1: Single. K2: Auto.
K3: Rising Edge Triggered
K4: Falling Edge Triggered
#7 X R/W
History command
Refer to table of history command for detail.
Default = H’0000
剩余21页未读,继续阅读
资源评论
weixin_38744153
- 粉丝: 347
- 资源: 2万+
上传资源 快速赚钱
- 我的内容管理 展开
- 我的资源 快来上传第一个资源
- 我的收益 登录查看自己的收益
- 我的积分 登录查看自己的积分
- 我的C币 登录后查看C币余额
- 我的收藏
- 我的下载
- 下载帮助
最新资源
- 昱感微融合产品YGW-L2集成了激光雷达,可见光摄像头,红外摄像头,多传感器融合后生成时空对齐的多维像素数据,通过GMSL接口发出 本品为客户提供更加直接、高效、和可扩展的环境与事件感知能力
- C#ASP.NET简易库存管理系统源码数据库 SQL2019源码类型 WinForm
- 昱感微融合产品YGW-L1集成了激光雷达,可见光摄像头,红外摄像头,多传感器融合后生成时空对齐的多维像素数据,通过GMSL接口发出 本品为客户提供更加直接、高效、和可扩展的环境与事件感知能力
- ansys Fluent阀门CFD分析
- 基于 SpringBoot 的宽带业务管理系统:构建智能化宽带业务运营新范式
- SpringBoot 视频点播系统:从设计蓝图到落地实现的探索之旅
- 使用 Fluent 在 2D 中模拟单个 气泡在水中上升 包括流畅的案例文件
- C#ASP.NET网盘管理源码数据库 Access源码类型 WebForm
- 深入解析 C++ std::thread 的.detach () 方法:原理、应用与陷阱
- Vue 条件渲染之道:v-if 与 v-else 的深度应用与最佳实践
资源上传下载、课程学习等过程中有任何疑问或建议,欢迎提出宝贵意见哦~我们会及时处理!
点击此处反馈
安全验证
文档复制为VIP权益,开通VIP直接复制
信息提交成功