Sinteso™ Cerberus™ PRO
ASD Aspirating smoke detector
FDA241, FDA221
Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET de-
tector line or for standalone operation
● Patented technology
● Early detection of a wider spectrum of particle sizes in the air
● Configuration using the USB interface or the control panel via FDCC221S (op-
tional)
● 'ASD Asyst-Tool' software to assist with pipe configuration
● Unique dust-resistant detection chamber
● Intuitive front indicator for airflow and smoke value
● Access to service functions
● Different event protocols
● Offline/online configuration supported
● Cleaning function (FDA241)
● 4…20mA output
A6V10331032_k_en_-- Smart Infrastructure
2021-06-28
2
Smart Infrastructure A6V10331032_k_en_--
2021-06-28
Properties
● Extended optical detection thanks to dual wavelengths (blue and infrared): The aspirat-
ing smoke detectors FDA241 and FDA221 use dual-wavelength technology to trigger an
alarm at the earliest possible moment. They are designed to protect small and medium-
sized business-critical environments for monitoring areas of up to 800m
2
(FDA241) or
500m
2
(FDA221). The detectors continually suck in air through a pipe system via their
aspirating holes. The air is fed into a uniquely designed detection chamber, in which tiny
smoke particles are detected by scattered light.
● Lower mounting and service costs: The aspirating smoke detectors FDA241 and
FDA221 can be used on an FDnet/C-NET detector line. For this purpose, communication
transponder FDCC221S is required.
● Configuration using the USB interface or the control panel via FDCC221S (optional): All
detector configurations, maintenance work, and alarm and fault management processes
can be carried out at a central location – the fire control panel. This ensures better con-
trol while also reducing the costs of the overall solution.
● 'Out-of-the-box' mounting and commissioning: Installation is simple thanks to combined
functions for normalizing smoke values and airflow, as well as appropriate presettings for
alarm and fault thresholds.
● ASD filter box FDAZ292 available as an accessory: Dust and other dirt is filtered out of
the aspirated air and does not get into the aspirating smoke detector. The filters in the
ASD filter box are easy to replace.
Use
Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms
and equipment. They are especially suited to applications in which point detectors are
pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a connec-
ted pipe system with defined aspirating holes. The air is supplied to the detection chamber
and is analyzed for smoke particles using the detector installed there. The sensitivity of the
detector can be adjusted.
The position and size of the aspirating holes is calculated using the 'FXS2056ASDAsyst
ToolV2' software. The calculation ensures that the air passes from the aspirating hole to the
detector in the time specified and with the required calculated sensitivity.
The 'FXS2056ASDAsyst ToolV2' software replaces the 'FXS2055ASD Asyst Tool' soft-
ware.
Examples of application
● Cavities such as false ceilings or false floors
● Clean rooms
● Rooms the height of which is greater than that permitted for point detectors
● Rooms with electromagnetic fields which influence the function of point detectors
● Large rooms up to 800m²
● Separate monitoring of control cabinets and electronics cabinets
● Data centers
● Telecommunication centers
● Mounting lines
● Cable tunnels
● Conveyor belts
Applications with a filter box
● Rooms with polluted air, in which the pollution has impaired the performance of optical
point detectors
● Mounting lines
● Recycling facilities
● Cement factories
3
Smart Infrastructure A6V10331032_k_en_--
2021-06-28
● Mining industry
● Subway stations
● Agricultural operations
● All other applications with visible dust load
Functions
Indication
The display contains clear, comprehensible bar graphs for smoke and airflow, as well as an
alarm indicator, an error indicator, and a dust indicator (FDA241).
When the housing cover is open, the operator has access to the 'Reset', 'Normalize Smoke',
and 'Normalize Flow' functions, as well as the mini USB connector.
Fig.1: Front indicatorFDA241
Fig.2: Front indicatorFDA221
Legend for the response indicators
Operation Flow warnings Smoke alarm Info alarm