SYNTHESIS
Operations Manual
single phase 115 V 0.2 - 0.75 kW
single phase 230 V 0.2 - 2.2 kW
three phase 400 V 0.75 - 2.2 kW
ISO 14001
MANAGEMENT SERVICE
UNI EN ISO 9001Certificato n° 50 100 0125
N3878
Operations Manual
Table of Contents
Foreword........................................................................................1
Examination before installation......................................................2
Chapter 1 Safety Precautions
1. Precautions for Operation........................................3
2. Environmental Precautions......................................6
Chapter 2 Hardware Instruction and Installation
1. Operational Environment .........................................7
2. Sample Model No. Identification ..............................8
3. Specifications...........................................................9
4. Wiring diagram.......................................................15
5. Dimensions & Location of terminal block...............19
Chapter 3 Software Index
1. Keypad Operating Instructions ..............................29
2. Parameters List......................................................30
3. Parameter Function Description ............................31
4. Malfunction Indication and Countermeasure .........43
5. General Malfunction Examination Method.............46
Chapter 4 Maintenance and Examination
1. Maintenance and Examination.............................48
Chapter 5 Option and accessories
1. Class B Emi filter...................................................50
2. Braking resistors ...................................................51
1. Foreword
To fully employ all functions of this AC Drive, and to ensure the safety for its users, please read
through this operations manual in detail. Should you have any further questions, please feel
free to contact your local distributor or regional representative.
�Please use Precaution with this product
The AC Drive is a power electronic device. For safety reasons, please read carefully those
paragraphs with “WARNING” or “CAUTION” symbols. They are important safety precautions to
be aware of while transporting, installation, operating or examining the AC drive. Please follow
these precautions to ensure your safety.
WARNING
Personnel injury may be resulted by improper operation.
CAUTION
The AC Drive or mechanical system may be damaged by improper operation.
WARNING
Do not touch the PCB or components on the PCB right after turning off the power before the
charging indicator went off.
Do not attempt to wire circuitry while power is on. Do not attempt to examine the components
and signals on the PCB while the inverter operating.
Do not attempt to disassemble or modify internal circuitry, wiring, or components of the
inverter.
The grounding terminal of the inverter must be grounded properly with 200V class type III
standard.
This is a product of the restricted sales distribution class according to EN61800-3.
In a domestic environment this product may cause radio interference in which case the user
may be required to take adequate measures.
CAUTION
Do not attempt to perform dielectric strength test to internal components of the inverter. There
are sensitive semiconductor-devices vulnerable to high voltage in the inverter.
Do not connect the output terminals: T1 (U), T2 (V), and T3 (W) to AC power input
The CMOS IC on the primary PCB of the inverter is vulnerable to static electrical charges. Do
not contact the primary PCB of the inverter.
1
2. Examination before installation
Every inverter has been fully tested and examined before shipment. Please carry out the
following examination procedures after unpacking your AC inverter.
Check to see if the model number of the AC inverter matches the model number of the AC
inverter that you ordered.
Check to see whether any damage occurred to the AC inverter during shipment. Do not
connect the AC inverter to the power supply if there is any sign of damage.
Report this to a regional sale representative if you find any abnormal condition as mentioned
above.
2
Chapter 1: Safety Precaution
1. Precautions for operation
Before turning ON power
CAUTION
Choose the appropriate power source with correct voltage settings for the input voltage
specification of the AC inverter.
WARNING
Special care must be taken while wiring the primary circuitry panel. The L1 and L2
terminal must be connected to the input power source and must not be mistakenly
connected to T1, T2 or T3 out put terminals. This may damage the inverter when the
power is turned on.
CAUTION
Do not attempt to transport the inverter by the front of the cover. Securely hold the
inverter by the heat-sink mounting chassis to prevent the inverter from falling, this
may cause personnel injury or damage to the inverter itself.
Install the inverter onto a firm metal base plate or another non-flammable type
material. Do not install the inverter onto or nearby any flammable material.
An additional cooling fan may need to be installed if several inverters are installed
into one control panel. The inside temperature inside an enclosed panel should be
below 40 degrees to avoid overheating.
Turn off the power supply before proceeding to remove or perform any work on any
panel. Carry out installation procedures according to instructions given in order to
avoid a situation resulting in an operational malfunction.
Suitable for use on a circuit capable of delivering not more than 5000 RMS
symmetrical amperes. 240 Volts maximum.
This product is not provided with over speed protection.
Only intended for use in a pollution degree 2 macro environment or equivalent