没有合适的资源?快使用搜索试试~ 我知道了~
E241994-B88
需积分: 0 0 下载量 75 浏览量
2023-10-12
15:22:38
上传
评论
收藏 71KB PDF 举报
温馨提示
试读
12页
E241994-B88
资源推荐
资源详情
资源评论
File E241994
Project 08CA14548
April 01, 2008
REPORT
On
COMPONENT - SYSTEMS, ELECTRICAL INSULATION
Huizhou Yongjin Electric Co Ltd
Huizhou Guangdong, China
Copyright © 2008 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce this Report provided it is reproduced in its entirety.
Underwriters Laboratories Inc. authorizes the above-named company to
reproduce the latest pages of that portion of this Report consisting of this
Cover Page through Page 4.
File E241994 Vol. 1 Sec. 2 Page 1 Issued: 2008-04-01
and Report
DESCRIPTION
PRODUCT COVERED:
Component - Systems, Electrical Insulation.
USR - Class 130(B) insulation system, designated YJ-B88.
GENERAL CHARACTER:
The insulation system covered by this Report is for use in transformer motor
or coil constructions.
RATINGS:
System
Designation
Insulation
Class
Maximum Hot Spot
Temperature
Indoor
Outdoor
(Enclosed)
YJ-B88
130(B)
130C
Yes
Yes
The maximum working voltage, and Basic Impulse Level (BIL) if applicable,
of this insulation system is 600 V.
The insulation system has been evaluated for use at a rated voltage
corresponding to the low voltage distribution network where transient overvoltages
are limited and partial discharge is not likely to contribute to the degradation
of the insulation system. This use is consistent with systems extending from the
service point or source of power operating at not more than 600 V nominal according
to the National Electrical Code, NFPA 70. This application is also consistent with
systems extending from the consumer's service in Low-Voltage or Extra-low voltage
applications at not more than 750 V according to the Canadian Electrical Code,
C22.1 and low-voltage mains of 1000 V ac or less in overvoltage category IV
installations according to Electrical Installations of Buildings, IEC 60364.
USR indicates investigation to UL Standard UL1446.
File E241994 Vol. 1 Sec. 2 Page 2 Issued: 2008-04-01
and Report
TECHNICAL CONSIDERATIONS (NOT FOR FIELD REPRESENTATIVE USE):
Use - For use only in products where the acceptability of the combination
is determined by Underwriters Laboratories Inc.
1. The acceptability of construction features of the transformer motor or coil
assemblies, such as spacings, insulation thicknesses (greater than those
specified under "Construction Details"), thickness and voltage rating of
lead insulation (if applicable), etc., shall be determined in the end-use
application.
2. The suitability for use when exposed to oil, chemicals, refrigerant, soaps,
x-rays, ultraviolet light and the like, has not been determined by this
investigation.
3. The only materials listed in these insulation systems that have been
evaluated for their long term electrical capabilities are those materials
listed as Ground Insulation, Interwinding Insulation, Magnet Wire
Insulation, Filament Wire Insulation, Winding Wire Insulation and
Encapsulants. All other materials listed in these insulation systems have
only been evaluated for chemical compatibility. As a result the long term
reliability of these other materials, such as potting compounds, tapes,
minor sheet insulation, etc., as electrical insulation or as a means to
reduce spacings has not been evaluated as part if this Recognition.
4. Ground insulation, in at least the minimum thickness specified, must always
be used between the windings and grounded metal and/or the magnetic cores
of devices. Ground insulation for motors may be referred to as slot
insulation. Materials not listed under ground and interwinding insulation
may not be used for these functions even if listed elsewhere in the system
description.
5. Interwinding insulation, in the minimum thickness specified, must always
be used between any two isolated windings in a transformer, with the
exception that it is not required between the series-parallel winding of
multivoltage devices. Materials not listed under ground and interwinding
insulation may not be used for these functions even if listed elsewhere in
the system description.