S7-1200 固件版本V4.x无法通过DASSidirect通讯的解决方法
需积分: 9 4 下载量 22 浏览量
2022-05-25
09:14:57
上传
评论
收藏 666KB PDF 举报
温馨提示
试读
5页
S7-1200 固件版本V4.x无法通过DASSidirect通讯的解决方法
资源详情
资源评论
资源推荐
NewSiemensS71200and1500PLCwithFirmwareV4.xandUpSupport
LegacyNumber#
DocID: TN1099
Version: 2.0
LastModified: 01/07/2016
SUMMARY
AfterSiemensreleasedthenewerfirmwareV4.0andthereafter,manycustomersreportedtheycannolongergetdataupdateswithWonderwareDASSidirect..
AfterthenewFirmwareV4.xreleasefortheS71500andS71200PLCfamily,manycustomersfoundthemselvesnolongerabletogetdataupdatefromthosenewlyupgradedPLCs.Thereasonwasthatthe
newSiemensPLCfirmwareaddednewfeaturesthatkeepPLCDBfromsharingthedata.InfactnotsharingDBisthedefaultsetting.
AnothernewfeatureinthenewPLCFirmwarereleasesupportssymbolicitemnamingwhereyoucanassigntheplcdatablocksandelementswithmoredescriptivesymbolicnames,andallowtheclient
applicationandinterfacedrivertoaccesstheDBwiththesymbolicnamesasitemnames.
ThisTechNoteprovidestheWonderwareDASSiDirectinformationneededtogetconsistentdataaccessfromtheS71200and1500PLCwiththosenewfeatures.
SITUATION
SincethesecurityprotectionfeaturewasaddedinthePLCside,thestepsinthisdocumentneedonlytobeimplementedinthewithinthePLC.YouwillneedtohaveaccesstotheStep7ornewTIAprograming
software.OncethechangesaremadeinthePLC,WonderwareDASSidrectwillbeabletogetdatawithoutanyadditionalconfiguration.
Figure1:SiemensTIAProgrammingSoftwareStartupWindow
Note:ThenewsymbolicnamefeatureissupportedonlywithWonderware'snewOIServerinterface.ThefeatureisnotsupportedbythelegacyDAServerDASSiDirectV3.xorprior.
SYMPTOMS
Theissues:
DAServergetsnodataupdatefromthePLC,regardlessthedatatype,orupdateinterval.YoucanpingthePLCIPaddress,anddataport102isopenedproperlytestedbytheportqryutility.
DAServergetspartialdataupdatesfromarraysanddatablocks.Somedataregisters(usuallythefirstelementinanarray)updatefine,someothers(therestofelementsinanarray)arenotupdated.
ACTION
Symptom1:TheDAServergetsnodataupdates
ThesolutionistoenablethePUT/GETprogrammingAccessPermitparameter.CompletethefollowingstepstoenablethePUT/GETsetting.
1. OpentheProjectintheTIAprogrammingsoftware.
Figure2:OpentheProjectintheTIAprogrammingsoftware
2. Selecttheproject,andclickOpen.Inthisexamplewe'reworkingwithProject1.
3. Onceintheproject,fromthelistontheleftside,selectthePLCProgrammingitemanddouble-clickit.
LegalInformation|PrivacyPolicy