Release Notes
ControlLogix Enhanced Redundancy System, Revision
20.055_kit2
Redundancy Module Catalog Numbers
1756-RM, 1756-RMXT, 1756-RM2, 1756-RM2XT
Controller Catalog Numbers
1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73, 1756-L73XT,
1756-L74, 1756-L75
Communication Module Catalog Numbers
1756-CN2/B, 1756-CN2R/B, 1756-CN2RXT/B, 1756-EN2T/D, 1756-EN2TR, 1756-EN2TXT, 1756-EN2TRXT, 1756-EN2F
These release notes describe enhancements, corrected anomalies, known
anomalies, restrictions, and application notes regarding enhanced redundancy
system revision 20.055_kit2 or earlier.
Topic Page
About This Enhanced Redundancy Firmware Bundle 2
Compatible Software Versions 5
About the Redundancy Module Configuration Tool 6
Enhancements 7
Corrected Anomalies 9
Known Anomalies 12
Restrictions 15
Application Notes 18
Upgrade the RSLogix 5000 Software Version 26
Replace 1756-EN2T Modules 28
Upgrade the RSLogix 5000 Software Version and Replace 1756-EN2T Modules 32
Upgrade Ethernet Modules When Rotary Switches Are Set between 2…254 34
Upgrade by Using Redundancy System Update 41
Replace 1756-RM/B (or earlier) Modules with 1756-RM2 Modules 58
Storing a Project to a Nonvolatile Memory Card While Your Process Is Running 59
Additional Resources 62
Rockwell Automation Publication 1756-RN694H-EN-P - December 2013
2 ControlLogix Enhanced Redundancy System, Revision 20.055_kit2
About This Enhanced
Redundancy Firmware Bundle
This enhanced redundancy firmware bundle, identified as revision 20.055_kit2,
contains series and firmware revisions for each of the modules listed in
Table 1.
You can download the firmware bundle at the Product Compatibility and
Download Center:
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page?.
Information that has been added or changed since the last revision of this
publication is indicated by a change bar as shown next to this paragraph. In
addition to information specific to the most recent firmware revision, the
information from previous minor revisions is retained in these release notes.
We strongly recommend that you review the information provided regarding
previous firmware revisions. We recommend that you do so because if you are
upgrading your firmware through multiple previous revisions, all of the
information specific to all of the revisions is applicable..
This enhanced redundancy system revision supports the following:
• Use of the 1756-EN2T/D module
• Use of RSLogix 5000 software, version 20.03.00
IMPORTANT
Throughout this publication, the following applies:
• References to the 1756-EN2T/D modules also apply to the
1756-EN2TXT/D modules.
• References to the 1756-EN2T/C (or earlier) modules also apply to the
1756-EN2TXT/C (or earlier) modules.
• Catalog numbers 1756-RM2 and 1756-RM2XT refer to the series A modules.
Catalog numbers 1756-RM2/B refer to series B modules.
IMPORTANT
When designing, installing, and operating the redundant chassis pair for this enhanced
redundancy system revision, you can use only the modules specified in Table 1.
Also, keep in mind the series and firmware revision requirements listed apply only to
components used in the redundant chassis pair, not to components used with
the redundancy system outside the redundant chassis pair.
Rockwell Automation Publication 1756-RN694H-EN-P - December 2013
ControlLogix Enhanced Redundancy System, Revision 20.055_kit2 3
Table 1 - Required Series and Firmware Revisions for Components Used in an Enhanced
Redundancy System, Revision 20.055_kit2
Cat. No. Module Description Series Firmware
Revision
1756-CN2 ControlLogix ControlNet bridge module B 20.020
1756-CN2R ControlLogix redundant media ControlNet bridge module
1756-CN2RXT ControlLogix-XT™ redundant media ControlNet bridge module
1756-EN2T ControlLogix EtherNet/IP bridge module D 10.006
(1)(2)
(1) IMPORTANT: The 1756-EN2T/D modules do not support firmware revisions previous to revision 10.006. Do not attempt to flash the
firmware to previous revisions.
(2) Firmware revision 10.006 is digitally-signed. For more information on digitally-signed firmware, see page 4.
C or earllier 5.008 or
5.028
(3)
(4)
(3) IMPORTANT: The 1756-EN2T/ C (or earlier) modules do not support firmware revision 10.006. Do not attempt to flash the firmware
to revision 10.006.
(4) Firmware revision 5.028 is digitally-signed firmware. Firmware revision 5.008 is unsigned firmware. For more information on
digitally-signed firmware, see page 4.
1756-EN2TR ControlLogix EtherNet/IP communication module Any 5.008 or
5.028
(3)
(4)
1756-EN2F ControlLogix EtherNet/IP fiber communication module
1756-EN2TXT ControlLogix-XT EtherNet/IP bridge module D 10.006
(1)
(2)
C or earlier 5.008 or
5.028
(3)
(4)
1756-EN2TRXT ControlLogix-XT EtherNet/IP redundant bridge module Any 5.028
1756-L61 ControlLogix5561 controller Any 20.055
1756-L62 ControlLogix5562 controller
1756-L63 ControlLogix5563 controller
1756-L63XT ControlLogix-XT controller
1756-L64 ControlLogix5564 controller
1756-L65 ControlLogix5565 controller
1756-L71 ControlLogix5571 controller
1756-L72 ControlLogix5572 controller
1756-L73 ControlLogix5573 controller
1756-L73XT ControlLogix-XT controller
1756-L74 ControlLogix5574 controller
1756-L75 ControlLogix5575 controller
1756-RM2 ControlLogix redundancy module Any 20.004
1756-RM2XT ControlLogix-XT redundancy module
1756-RM ControlLogix redundancy module Any 3.003
1756-RMXT ControlLogix-XT redundancy module
Rockwell Automation Publication 1756-RN694H-EN-P - December 2013
4 ControlLogix Enhanced Redundancy System, Revision 20.055_kit2
1756-EN2T Modules Digitally-signed Firmware
Digitally-signed firmware provides additional security over the unsigned
firmware. This firmware is different based on the EtherNet/IP communication
modules you use.
• 1756-EN2T/D modules - Support only firmware revision 10.006. This
firmware revision is digitally-signed.
• 1756-EN2T/C (or earlier) modules - Support firmware revisions 5.008 or
5.028 in this enhanced redundancy system, revision. Consider the
following:
– Firmware revision 5.008 is unsigned firmware.
– Firmware revision 5.028 is digitally-signed firmware.
Digitally-signed and Unsigned Firmware Availability
When using EtherNet/IP communication modules in an enhanced redundancy
system, revision 20.055_kit2, remember the following:
• Firmware revision 10.006 is included with the enhanced redundancy
systems, revision 20.055_kit2 firmware bundle.
• Firmware revision 5.008 is included with the enhanced redundancy
systems, revision 20.055_kit2 firmware bundle.
• Firmware revision 5.028 is not included in the enhanced redundancy
system, revision 20.055_kit2. You must download and install this
digitally-signed firmware after the redundancy bundle is installed.
You can download firmware revision 5.028 and the enhanced redundancy system,
revision 20.055_kit2 firmware bundle at the Product Compatibility and
Download Center:
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page?.
The firmware bundle is identified as V20.055_kit2.
IMPORTANT
When you install the digitally-signed firmware, that is, firmware revision
5.028, into a 1756-EN2T/C (or earlier) module, the installation makes the
module incompatible with some firmware revisions.
For example, after upgrading firmware, the module supports use of only
digitally-signed firmware. Any unsigned firmware updates are rejected by the
module.
Rockwell Automation Publication 1756-RN694H-EN-P - December 2013
ControlLogix Enhanced Redundancy System, Revision 20.055_kit2 5
Compatible Software Versions
Use these versions of software with this redundancy firmware bundle.
FactoryTalk View Software Considerations
FactoryTalk View software is required for only these human-machine interfaces
(HMIs):
• PanelView™ Plus terminal
• VersaView
®
industrial computer running a Windows CE operating system
• FactoryTalk View Supervisory Edition software
Table 2 - Required Software Versions for Enhanced Redundancy System, Revisions 20.055_kit2
Software Required Software Version, Min
CompareTool 3.20.02
ControlFLASH™ 12.00.01
FactoryTalk® Services Platform 2.50.00 (CPR 9, SR5)
FactoryTalk Activation 3.50.00 (CPR 9, SR5)
FactoryTalk Alarms and Events 2.40.00 (CPR 9, SR4)
FactoryTalk Batch 11.00.00
(2)
(2) Use the most recent FactoryTalk Batch Patch Roll-up with this enhanced redundancy firmware revision. For the most recent patch
roll-up, see Rockwell Automation Knowledgebase Answer ID 59058, accessible at:
http://www.rockwellautomation.com/knowledgebase/.
For system requirements, go to http://www.rockwellautomation.com/rockwellsoftware/design/rslogix5000/sysreq.html.
FactoryTalk View Site Edition 6.10.00 (CPR 9, SR4)
Redundancy Module Configuration Tool 8.01.05
RSLinx® Enterprise 5.50.04 (CPR 9, SR5)
RSLinx Classic 2.59.01 (CPR 9, SR5)
RSLogix™5000
(1)
(1) If you choose to use RSLogix 5000 software, version 20.03.00, we strongly recommend you read Upgrade the RSLogix 5000 Software
Version on page 26 before proceeding.
20.01.00 (CPR 9, SR5)
20.03.00 (CPR9, SR5)
RSNetWorx™ for ControlNet 11.00.00 (CPR 9, SR5)
RSNetWorx for EtherNet/IP
剩余65页未读,继续阅读
资源评论
yuanyanshun123
- 粉丝: 0
- 资源: 43
上传资源 快速赚钱
- 我的内容管理 展开
- 我的资源 快来上传第一个资源
- 我的收益 登录查看自己的收益
- 我的积分 登录查看自己的积分
- 我的C币 登录后查看C币余额
- 我的收藏
- 我的下载
- 下载帮助
最新资源
资源上传下载、课程学习等过程中有任何疑问或建议,欢迎提出宝贵意见哦~我们会及时处理!
点击此处反馈
安全验证
文档复制为VIP权益,开通VIP直接复制
信息提交成功