APPENDIX
A
DATA SHEETS FOR IEEE 14 BUS SYSTEM
T
he
IEEE 14 bus system is shown in figure 3.1. The system data is taken
from [9]. The data given in the following tables is on 100MVA base.
The minimum and maximum limits of voltage magnitude and phase angle are
considered to be 0.95p.u. to 1.05p.u. and -45
◦
to +45
◦
respectively.
126
Appendix A. IEEE 14 bus system 127
Table A.1: Line data – IEEE 14 bus system
Line From To Line impedance (p.u.) Half line charging MVA
number bus bus Resistance Reactance susceptance (p.u.) rating
1 1 2 0.01938 0.05917 0.02640 120
2 1 5 0.05403 0.22304 0.02190 65
3 2 3 0.04699 0.19797 0.01870 36
4 2 4 0.05811 0.17632 0.02460 65
5 2 5 0.05695 0.17388 0.01700 50
6 3 4 0.06701 0.17103 0.01730 65
7 4 5 0.01335 0.04211 0.00640 45
8 4 7 0 0.20912 0 55
9 4 9 0 0.55618 0 32
10 5 6 0 0.25202 0 45
11 6 11 0.09498 0.1989 0 18
12 6 12 0.12291 0.25581 0 32
13 6 13 0.06615 0.13027 0 32
14 7 8 0 0.17615 0 32
15 7 9 0 0.11001 0 32
16 9 10 0.03181 0.0845 0 32
17 9 14 0.12711 0.27038 0 32
18 10 11 0.08205 0.19207 0 12
19 12 13 0.22092 0.19988 0 12
20 13 14 0.17093 0.34802 0 12
Table A.2: Capacity and cost coefficients – IEEE 14 bus system
Generator
P
min
i
P
max
i
a
i
b
i
c
i
number (MW ) (MW ) ($/(MWhr)
2
) ($/MW hr) ($/hr)
G
1
10 160 0.005 2.450 105.000
G
2
20 80 0.005 3.510 44.100
G
3
20 50 0.005 3.890 40.600
Table A.3: Transformer tap setting data – IEEE 14 bus system
From bus To bus
Tap setting value (p.u.)
4 7 0.978
4 9 0.969
5 6 0.932
Appendix A. IEEE 14 bus system 128
Table A.4: Bus data – IEEE 14 bus system
Bus voltage Generation Load Reactive
Phase Real Reactive Real Reactive power
Bus Magnitude angle power power power power limits
number (p.u.) (degree) (MW ) (MVAR) (MW ) (MVAR) Q
min
(MVAR) Q
max
(MVAR.)
1 1.060 0 114.17 -16.9 0 0 0 10
2 1.045 0 40.00 0 21.7 12.7 -42.0 50.0
3 1.010 0 0 0 94.2 19.1 23.4 40.0
4 1 0 0 0 47.8 -3.9 – –
5 1 0 0 0 7.6 1.6 – –
6 1 0 0 0 11.2 7.5 – –
7 1 0 0 0 0 0 – –
8 1 0 0 0 0 0 – –
9 1 0 0 0 29.5 16.6 – –
10 1 0 0 0 9.0 5.8 – –
11 1 0 0 0 3.5 1.8 – –
12 1 0 0 0 6.1 1.6 – –
13 1 0 0 0 13.8 5.8 – –
14 1 0 0 0 14.9 5.0 – –
Table A.5: Shunt capacitor data – IEEE 14 bus system
Bus number Susceptance (p.u.)
9 0.19
APPENDIX
B
DATA SHEETS FOR IEEE 30 BUS SYSTEM
T
he
IEEE 30 bus system is shown in figure 3.3. The system data is taken
from [47]. The data given in the following tables is on 100MVA base.
The minimum and maximum limits of voltage magnitude and phase angle are
considered to be 0.95p.u. to 1.05p.u. and -45
◦
to +45
◦
respectively.
129
Appendix B. IEEE 30 bus system 130
Table B.1: Line data – IEEE 30 bus system
Line From To Line impedance (p.u.) Half line charging MVA Annual cost
number bus bus Resistance Reactance susceptance (p.u.) rating (×10
3
$/hr)
1 1 2 0.02 0.06 0.03 130 216.6125
2 1 3 0.05 0.20 0.02 130 307.2875
3 2 4 0.06 0.18 0.02 65 509.9500
4 2 5 0.05 0.02 0 130 721.5250
5 2 6 0.06 0.18 0.02 65 168.1750
6 3 4 0.01 0.04 0 130 700.000
7 4 6 0.01 0.04 0 90 474.3000
8 4 12 0 0.23 0 65 554.1250
9 5 7 0.05 0.12 0.01 70 62.2000
10 6 7 0.03 0.08 0 130 130.2000
11 6 8 0.01 0.09 0 32 104.6250
12 6 9 0 0.21 0 65 306.9000
13 6 10 0 0.56 0 32 20.9250
14 6 28 0.07 0.06 0.01 32 210.800
15 8 28 0.06 0.20 0.02 32 54.250
16 9 11 0 0.21 0 65 83.7000
17 9 10 0 0.11 0 65 927.6750
18 10 20 0.09 0.21 0 32 117.8000
19 10 17 0.03 0.09 0 32 167.4000
20 10 21 0.03 0.08 0 32 160.4250
21 10 22 0.07 0.15 0 32 195.3000
Continued on next page