Warning
This instruction sheet only provides introductory information on electrical specification, installation and wiring.
Switch off the power before wiring. DO NOT touch any terminal when the power is switched on.
IFD9506 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,
electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key
or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
Introduction
Features
Thanks for using the Delta industrial network converter. IFD9506 is the Ethernet converter. It supports the
protocol of the standard MODBUS TCP (eight sets of MODBUS TCP clients and sixteen sets of MODBUS TCP
servers). It supports eight sets of IP filters which filtering the accessible IP address. The network speed can be
up to 100 Mbps, and three external digital input points which can trigger the alarm to send the email is built in
IFD9506. Besides, IFD9506 is equipped with the cache and the function of resending the serial communication
which fails. The communication and the power supply are isolated from each other. Users can enjoy
high-speed Ethernet and high stability at the same time.
Product Profile & Outline
9
1
Communication ports: RS-485,
Ethernet, RS-232
2
Power indicator
3
Address switch
4
Data format/baud rate switch
5
Digit display
6
RS-485 indicator, Reset button,
Ethernet indicator
7
Module name
8
RS-485 connector, digital input points,
power input point, earth point
9
DIN rail connector
Specifications
Ethernet Interface
Connector RJ-45 with Auto MDI/MDIX
Transmission cable Category 5e, 100m (Max)
Transmission speed 10/100 Mbps Auto-Detection
Network protocol ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS TCP, Delta Configuration
RS-485 Interface
Connector RJ-11
Transmission cable Telecom Cable, 1200 m (Max)
Transmission speed
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200 bps
ENGLISH
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol MODBUS, User Define
RS-232 Interface
Connector Mini DIN
Transmission cable DVPACAB215 / DVPACAB230 / DVPACAB2A30
Transmission speed
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200 bps
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol MODBUS, Delta Configuration, User Define
Terminal Block
Connector Feed-through terminal 10PIN
Transmission cable Twisted pair
Transmission speed
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600,
115,200 bps
Communication format Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
Communication protocol MODBUS, User Define
Electrical Specifications
Power voltage 24V DC (-15% ~ 20%) supplied by feed-through terminal
Power consumption 3W
Insulation voltage 500V
Weight 140g
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±1KV,
Communication I/O: ±0.5KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
CS (IEC61131-2, IEC 61000-4-6): 150KHz ~ 80MHz, 3V/m
Surge (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
Operation/storage
Operation: 0ºC ~ 55ºC (temperature), 50 ~ 95% (humidity), pollution degree 2
Storage: -25ºC ~ 70ºC (temperature), 5 ~ 95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC
68-2-27(TEST Ea)
Certificates
Installation
Dimension
Unit: mm
Station Address Setting
Switch setting Content
01 … F7 Valid MODBUS station address
Data Format Switch
Switch setting Format
Switch setting Format
0 7-N-1 8 7-N-2
1 8-N-1 9 8-N-2
2 7-O-1
A 7-O-2
3 8-O-1
B 8-O-2
6 7-E-1
E 7-E-2
7 8-E-1 F 8-E-2
Baud Rate Switch
Switch setting Baud rate (bps)
Switch setting Baud rate (bps)
1 110
7 4,800
2 150
8 9,600
3 300
9 19,200
4 600
A 38,400
5 1,200
B 57,600
6 2,400
C 115,200
RJ-11 PIN Definition
PIN Signal Definition PIN Signal Definition
1 -- N/C
4 D- Negative pole for data
2 -- N/C
5 GND Ground
3 D+ Positive pole for data
6 -- N/C
RJ-45 PIN Definition
PIN Signal Definition PIN Signal Definition
1 Tx+
Positive pole for data
transmission
5 -- N/C
2 Tx-
Negative pole for data
transmission
6 Rx-
Negative pole for data
receiving
3 Rx+
Positive pole for data
receiving
7 -- N/C
4 -- N/C 8 -- N/C
RS-232 PIN Definition
PIN Signal Definition PIN Signal Definition
1 -- N/C 5 Tx Transmission data
2 -- N/C 6 -- N/C
3 -- N/C 7 -- N/C
4 Rx Reception data 8 GND Ground
Feed-through Terminal PIN Definition
PIN Signal Definition
1 SG Ground of signal
2 D- Data-
3 D+ Data+
4 X2 Digital input 2
5 X1 Digital input 1
6 X0 Digital input 0
7 S/S Ground of digital input
8 24V +24V
9 0V 0V
10 -- Earth ground
Communication Parameter Setting
When users use IFD9506 for the first time, they can set the network and the MODBUS (RS-232/RS-485)
communication parameters by means of the external switch and DCISoft. The external switch can be used to
set the communication address, the data format, and the baud rate. DCISoft is used to set the parameters such
as IP address. Users can set the communication through RS-232 or Ethernet. Please connect the computer
and IFD9506 by RS-232 or the Ethernet cable before doing the setting.
Setting the communication parameter by the software:
1. Opening DCISoft: Enter “Communication Setting” in “Tools”. Choose “Ethernet” or “RS-232” in
“Connection Setup”, and click “OK”. Click “Search” on the task bar to search for IFD9506. Finally, click the
picture twice to enter the page.
2. Setting the network: Enter the basic setting page, choose either “Serial Master” or “Serial Slave” as the
master configuration, and set the network parameters. The default IP address is 192.168.1.5. When users
need to convert the Ethernet packet into the RS-232/RS-485 data, they have to choose the master mode.
When users need to convert the RS-232/RS-485 data into the Ethernet packet, they have to choose the
slave mode.
3. Setting the serial communication: Users can set the serial communication parameters by means of the
external switch or DCISoft. Please notice that the station address can not be the same with the station
address of the device connected by RS-485.
Note: After IFD9506 is restarted, if the setting in the software does not conform to the setting of the switch,
the communication will be carried out in accordance with the hardware setting by the switch. Please refer to
IFD9506 Operation Manual for more information related to the setting.
LED Indicators & Trouble-Shooting
POWER LED
LED status Indication How to correct
Green light OFF No power supply Check the working power
Green light ON Working power is normal --
RS-485 LED
LED status Indication How to correct
Green light OFF No RS-485 communication
If the LED is off during the communication, check if the RS-485
connection of IFD9506 falls off.
Constantly ON Incorrect RS-485 connection Switch D+ and D-
Green light
flashes
RS-485 communication is
normal.
--
LINK/ACT LED
LED status Indication How to correct
Green light OFF Ethernet connection fails.
1. Check if the Ethernet cable is correctly connected.
2. Re-power IFD9506. If the error still exists, send your IFD9506
back to the factory for repair.
Green light ON
The connection is normal, but
no data transmission.
--
Green light
flashes
The data is being
sent/received.
--
Codes in Digital Display
Code Indication How to correct
01 ~ F7
MODBUS station address (in
normal operation)
--
F0 Returning to default setting --
F2 Working voltage is too low. Check if the working voltage is normal.
F3 Internal memory check error
1. Re-power IFD9506. If the error still exists, try step 2.
2. Reset IFD9506. If the error still exists, send it back to the factory
for repair.
F4 Factory setting error
1. Re-power IFD9506. If the error still exists, try step 2.
2. Reset IFD9506. If the error still exists, send it back to the factory
for repair.
F5 Network connection error Check if Ethernet is normally connected.
F6
Full number of devices
connected in the network
Check if the number of Ethernet connections is too much.
F7 UART setting error. Check if the RS-485, RS-232 data format is correct.
E1 Alarm 1 triggered Check Alarm Input Point 1.
E2 Alarm 2 triggered Check Alarm Input Point 2.
E3 Alarm 3 triggered Check Alarm Input Point 3.
04 CRC error
1. Check if the station address of the RS-485 device is the same
with that of the other device.
2. Check if the data format of all devices connected by the RS485
communication cable is consistent.
0b No response from the station
1. Check if the RS-485 communication cable is connected normally.
2. Check if the RS-485 station address is set incorrectly, and make
sure that the data format of all devices is consistent.
注意事項
此安裝手冊只提供電氣規格、一般規格、安裝及配線等。
配線時請務必關閉電源,請勿在上電時觸摸任何端子。
本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊∕
衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開),防止非維護人員操作
或意外衝擊本體,造成危險及損壞。
產品簡介
功能特色
感謝您採用台達轉換器。IFD9506 為 Ethernet 轉換器,支援標準 MODBUS TCP 通訊協定(MODBUS TCP Client
8 組,MODBUS TCP Server 16
組)。支援 8 組 IP Filter 功能,過濾可存取的 IP。網路速度最快可達 100 Mbps
傳輸速率,並內建三點外部數位輸入點可觸發警報發送電子郵件。另外具有資料快取與串列失敗重傳功能,搭配
通訊與電源全隔離,讓您在享受高速 Ethernet 同時並兼顧穩定性。
產品外觀
1
通訊口 RS-485, Ethernet,
RS-232
2
電源指示燈
3
站號設定開關
4
通訊格式、通訊速率設定開關
5
數位顯示器
6
RS-485 指示燈、Reset 按鍵、
Ethernet 指示燈
7
模組名稱
8
端子台 RS-485 連接器、數位輸入
點、電源輸入、大地
9
9
DIN 軌連接器
功能規格
Ethernet 介面
連接器
RJ-45 with Auto MDI/MDIX
線材 Category 5e, 100 公尺 (Max)
傳輸速率
10/100 Mbps Auto-Detection
網路協定
ICMP, IP, TCP, UDP, DHCP, SMTP, MODBUS TCP, Delta Configuration
RS-485 介面
連接器
RJ-11
線材 Telecom Cable, 1200 公尺 (Max)
傳輸速率
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps
繁體中文
通訊格式
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
通訊協定
MODBUS, User Define
RS-232 介面
連接器
Mini DIN
線材
DVPACAB215 / DVPACAB230 / DVPACAB2A30
傳輸速率
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps
通訊格式
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
通訊協定
MODBUS, Delta Configuration, User Define
端子台
連接器 歐式端子台 10PIN
線材 雙絞線, 1200 公尺 (Max)
傳輸速率
110, 150, 300, 600, 1,200, 2,400, 4,800, 9,600, 19,200, 38,400, 57,600, 115,200 bps
通訊格式
Stop bit: 1,2 Parity bit: None, Odd, Even Data bit: 7,8 ASCII/RTU
通訊協定
MODBUS, User Define
電氣規格
電源電壓 24V DC (-15% ~ 20%) 由歐式端子台輸入
消耗電力
3W
絕緣電壓
500V
重量
140g
環境規格
雜訊免疫力
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line:±1KV
Communication I/O: ±0.5KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1GHz, 10V/m. 1.4GHz ~ 2.0GHz, 10V/m
CS (IEC61131-2, IEC 61000-4-6): 150KHz ~ 80MHz, 3V/m
Surge (Biwave IEC61132-2, IEC61000-4-5):
Power line 0.5KV DM, Ethernet 0.5KV CM, RS-485 0.5KV CM
操作∕儲存環境
操作:0ºC ~ 55ºC(溫度)、50 ~ 95%(濕度)、污染等級 2
儲存:-25ºC ~ 70ºC(溫度)、5 ~ 95%(濕度)
耐震動∕/衝擊
國際標準規範 IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27(TEST
Ea)
標準
安裝
外觀
资源评论
weixin_38744375
- 粉丝: 372
- 资源: 2万+
上传资源 快速赚钱
- 我的内容管理 展开
- 我的资源 快来上传第一个资源
- 我的收益 登录查看自己的收益
- 我的积分 登录查看自己的积分
- 我的C币 登录后查看C币余额
- 我的收藏
- 我的下载
- 下载帮助
最新资源
- 使用特定版本的 Python 设置 GitHub Actions 工作流程.zip
- 汽车电子中MICROSAR OBD协议栈解决方案及其应用
- 基于Kotlin,AndroidX的仿微信图片选择器
- 平台重构与技术进化:汽车生态系统的未来发展
- HarmonyOs DevEco Studio小技巧34-鸿蒙应用架构设计 MVVM模式与三层架构
- pycharm为基础的人工智能课程设计
- 使用 Python 进行基础操作和高级操作 .zip
- 使用 Python 编写的 livereload 服务器.zip
- 终端(自己造的终端,亲测,和原版终端一模一样,连python命令也能使用)
- 使用 Python 类型提示进行数据验证.zip
资源上传下载、课程学习等过程中有任何疑问或建议,欢迎提出宝贵意见哦~我们会及时处理!
点击此处反馈
安全验证
文档复制为VIP权益,开通VIP直接复制
信息提交成功