Base units
PNOZ m1p
NSG-D-2-359-2006-02
Base units from the PNOZmulti modu-
lar safety system
Approvals
Unit features
` Can be configured in the
PNOZmulti Configurator
` Positive-guided relay outputs:
– 1 safety output in accordance
with EN 954-1, Cat. 4
or 2 safety outputs in accord-
ance with EN 954-1, Cat. 2
` Semiconductor outputs:
– 2 safety outputs in accordance
with EN 954-1, Cat. 4
or 4 safety outputs in accord-
ance with EN 954-1, Cat. 3
– 1 auxiliary output
` 4 test pulse outputs
` 1 cascading input and output
can also be used as a standard out-
put
` 20 inputs for connecting:
– E-STOP pushbutton
– Two-hand button
– Safety gate limit switch
– Reset button
– Light barrier
– Scanner
– Enable switch
– PSEN
– Operating mode selector switch
– Safety mat
` Muting function
` Max. 8 expansion modules and 1
fieldbus module can be connected
` LED indicator for:
– Diagnostics
– Supply voltage
– Output circuits
– Input circuits
` Test pulse outputs used to detect
shorts across the inputs
` Monitors shorts between the safety
outputs
` Plug-in connection terminals (either
cage clamp terminal or screw termi-
nal)
Unit description
The PNOZmulti modular safety system
is used for the safety-related interrup-
tion of safety circuits and is designed
for use in:
` Emergency stop equipment
` Safety circuits in accordance with
VDE 0113 Part 1 and EN 60204-1
Chip card
Chip cards are available with memo-
ries of 8 kByte and 32 kByte. For large-
scale projects we recommend the 32
kByte chip card (see chapter contain-
ing the order references).
The chip card with a memory of 32
kByte can only be used from
PNOZ m1p Version 2.0.
Safety features
The relay conforms to the following
safety criteria:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effec-
tive in the case of a component fail-
ure.
` The relay contacts meet the re-
quirements for safe separation
through increased insulation com-
pared with all other circuits in the
safety system.
` The safety outputs are tested peri-
odically using a disconnection test.
PNOZ m1p