崇左市行政中心大楼工程
施工单位:广西北流建工集团有限责任公司
编 制: 审核: 审 批:
编制日期:二○○四年六月十五日
1
目 录
1.工程概况.....................................................................................................................................1
1.1 基本概况 ........................................................................................................................1
1.2 施现场条件 ....................................................................................................................1
2.施工临时用电设计.....................................................................................................................1
2.1 编制依据 ........................................................................................................................1
2.2 初步设计 ........................................................................................................................2
2.3 用电量计算 ....................................................................................................................2
2.3.1 主干线路 L1 用电量计算..................................................................................2
2.3.2 主干线路 L2 用电量计算..................................................................................4
2.3.3 主干线路 L3 用电量计算..................................................................................5
2.3.4 主干线路 L4 用电量计算..................................................................................6
2.3.5 支线路 L5 用电量计算......................................................................................6
2.3.6 支线路 L6 用电量计算......................................................................................7
2.3.7 支线路 L7 用电量计算......................................................................................8
2.3.8 支线路 L8 用电量计算......................................................................................9
2.3.9 支线路 L9 用电量计算:..................................................................................9
2.3.10 支线路 L10 用电量计算...............................................................................11
3.施工用电管理措施...................................................................................................................11
3.1 技术措施 ......................................................................................................................11
3.1.1 接地与防雷 ......................................................................................................11
3.1.2 电气设备设置 ..................................................................................................12
3.1.3 漏电保护装置 ..................................................................................................12
3.1.4 电器设备安装 ..................................................................................................13
3.1.5 电气设备的使用和维护 ..................................................................................13
3.1.6 施工现场的电缆线路 ......................................................................................14
3.1.7 施工现场的室外架空线路 ..............................................................................14
3.1.8 灯具的安装规定 ..............................................................................................15
3.2 用电组织管理 ..............................................................................................................15
3.2.1 用电管理规定 ..................................................................................................15
3.2.2 电箱管理规定 ..................................................................................................16
3.2.3 电气安全生产管理规定 ..................................................................................16
3.2.4 电工操作规程 ..................................................................................................16
3.2.5 预防电气火灾措施 ..........................................................................................16
3.3 安全技术交底 ..............................................................................................................17
3.3.1 安全用电自我防护技术交底 ..........................................................................17
3.3.2 电工安全技术交底 ..........................................................................................17
3.3.3 机械安全技术交底 ..........................................................................................18
3.4 安全技术档案管理 ......................................................................................................18
1
1.工程概况
1.1 基本概况
本工程是崇左市行政综合大楼,工程地点位于崇左市城南新区石林大道的北侧,龙峡山南
侧。占地 394 亩,办公大楼占地 18000㎡,建筑面积 67000 多㎡。其中:A 区为 9981㎡,B 区
为 13933㎡,C 区为 14709㎡,D 区为 13933㎡,E 区为 9981㎡,F 区为 5351㎡。是崇左市的
市委、市政府、市人大、市政协四大领导班子的行政活动中心、行政办公场所,也是人民群众
开展文体活动和休闲娱乐活动的公共场所。是崇左市的标志性建筑。
平面布置形式:A、E 区为转角形布置;B、D 区为梯形布置;C 区为矩形布置。C、D、E
区分别相连。A 区与 E 区、B 区与 D 区分别为对称设计。见下图。
本工程由华南理工学院设计研究院和南宁市建筑设计院共同设计,广西建设监理公司监理。
工程内容包括:土建、水暖卫、安装、消防等工程。
1.2 施现场条件
本工程地处崇左市城南新区,场地已平整。新区内有一条简易道路进入,能满足施工运输
的需要。由于是新区,市政设施尚未完善,场地内无排水系统。现场北面接有 DN150 给水管。
供电系统已接至北面。
2.施工临时用电设计
2.1 编制依据
施工现场临时用电安全技术规范(JGJ46-88)
建设工程施工现场供用电安全规范(GB50104-93)
建筑电气安装工程施工质量验收规范(GB50303-2002)
2
2.2 初步设计
在场地 D 区的北面约 200m,已有 2 台电力变压器,变压器的容量为 615、500KVA,能
满足施工用电的需要,不需再安装变压器。本工程的施工用电从该变压器引出,接至施工现场。
a、本用电设计仅负责施工现场总开关箱以下的线路,主要是基础施工用电、主体施工用
电、装饰装修工程用电和照明用电的电气开关的选择、布置、使用、维护和管理。
b、本工程供电计划按两个线路进行,其中线路 L1 负责 B、C、D 区的塔吊和钢筋加工以
该三栋楼的楼层用电;线路 L2 负责 A 区的所有用电;线路 L3 负责 E 区塔吊、井架、钢筋加
工、搅拌站及 B、C、D 区搅拌站供电,线路 L4 负责生活区照明用电。
c、本供电系统采用三相五线制(TN-S 系统),三级配电、二级保护或三级保护。其中要
求首级保护漏电不大于 80mA,主要保护总配电箱至分配电箱电线漏电,漏电时间系数不大
于 0.1S。开关箱和流动电箱不大于 30mA,漏电时间保护系数也不大于 0.1S。
d、根据施工现场用电设施布置情况,采用单元配电法,用一组电线从原有的配电箱(变
压器)引至施工现场,再采用多元配电线路将 4 组电线从总配电箱分布到分配电箱。从分配
电箱分支电路到开关箱,应当配电合理,互不干扰防止因电气故障影响施工。
e、应保证施工现场用电达到规范化管理。
f、电线分布
见临时用电平面布置图
g、进楼层采用电缆按供电,电缆随楼层上升,电缆每层固定一次,必须将电缆固定好。
h、现场采用投射灯 5 盏,普通照明灯若干。
i、各楼层用电的开关箱从附近的配电箱引接。
2.3 用电量计算
2.3.1 主干线路 L1 用电量计算
本线路施工机械用电量主要是 A 区的生产用电量。
3
总线路 L1 施工机械用电量统计表
序号
名 称
规格型号
数量
单台功率
(KW)
合计功率
(KW)
1
砼搅拌机(站)A 区
HL1-20
2
18.5
37
2
砼输送泵
HBJ60A
1
75
75
3
砂石自动配料机
HP500
1
25
25
4
砂浆搅拌机
UTZ300A
2
3.0
6
5
塔吊
QTZ5211
1
54
54
6
木工圆锯
φ300
3
3.0
9
7
抽水机
D=50
4
1.5
6
8
钢筋切割机
GW40-1
3
3
3
9
钢筋弯曲机
GJ-40
3
3
3
10
钢筋调直机
MJ-1
1
4
4
11
蛙式打夯机
HW-60
2
2.8
5.6
12
平板振动器
PZ-50
2
2.0
4
13
插入式振动器
HZ-50
2
1.1
2.2
小计
27
∑1=235.6
14
电渣压力焊机
MH136
1
20 KVA
20
15
闪光对焊机
NU1-100
1
75 KVA
75
16
电弧焊机
BX-330
1
21 KVA
21
小计
3
∑2=116
合计
30
∑=351.6
由于在本线路的用电机具已达 27 台,其中电焊机为 3 台,则取 K
1
=0.5,K
2
=0.6,cosφ取 0.75
按允许电流选择导线截面,该线路 L1 的工作电流为:
A
U
PK
I 379
75.03803
1000)1166.06.2355.0(
cos3
�
��
����
�
��
�
�
�
线
线
根据以上电流量查表可知,选用 BLV 导线,截面为 4×185mm
2
,其允许电流为 380A>379A,
可以满足要求。
接地线选用 70mm
2
。