WG 13 CIM Issues and Update Report
Updated 2009-11-09
1. Introduction
This document summarizes the CIM issues and changes for CIM 14 up to the document
date. Included are changes from IEC 61970 CIM13 (CIM13v19) to the current working
draft listed under Referenced Documents.
Change tracking is contained in the Microsoft Word version of this document from the
previous release of this document.
2. Referenced Documents
[1] CIM_issues_2009081920091109.xls
[2] CIM_changes_2009081920091109.xls
[3] iec61970cim14v123_iec61968cim10v25_combined.eap
3. Process for Content of this Document
This document was created to reflect all open issues in the referenced issue spreadsheet.
Each open issue appears one time in this document under one category that most closely
represents the issue. As issued are closed they will remain in this document and be
presented as closed issues in the final CIM14 report. This document will be updated
throughout the year to facilitate discussion and will ultimately become the final issue
report for the CIM14 release.
4. CIM14 Release
4.1.Changed in CIM 14
All changes to the UML for IEC61970CIM14 are documented in reference [2]. It is
assumed all changes for CIM14 are based on the release of CIM13r19 as the official
CIM13 release. Highlights of changes include:
Extensions added to support UCTE exchange
Company class removed.
Moved several classes from 61970 to Assets package in 61968
HeatExchanger class removed.
Removed datatypes ShortLength and LongLength and replaced them with Length.
Removed classes Load, CustomerLoad, and InductionMotorLoad.
4.2.Issues Closed in CIM 14
150 – Company as owner and operator. Resolved with 1105.
196 We've come across 16 relation... (deferred) (was missing cardinality fixed?)
204 – Part 301. Changes made previously, but not closed.
205 Many associations have inadequate or no documentation...
206 Need to have a way to translate the documentation fields...
240 How should the Precondition area in an Incremental file be used
241 - Measurement multiplicity needs review, Violation of CIM rules for Measurement.
Changed as suggested.
244 - There are at least three ways to model regulation (possibly fixed in CIM 12).
245 – partial model unclear
250 – CAISO proposal for model versioning and model for an RDF/XML file
251 - Need to add a flag on the measurement/measurement value...
253 Phase-shifter transformer...
255 – Current capacity in SeriesCapacitor – No change
256 – Current capacity in ACLineSegment – No change
261 In Tapchangers, we only have a stepVoltageIncrement...
266 How do we modelize an Autotransformer with CIM model ?
279 – AutoProducer – Agreed to close old issue. – No Change.
285 – Measurement-PSR – Changed cardinality
296 Is there a rule concerning the sign of the susceptance of the TransformerWinding...
306 How to model a compensating tertiary winding in a transformer (possibly solved in
IOP 10, CIM 12)
311 – Jointly owned units. Fixed with OperatingParticipant and OperatingShare.
312 – Does Company serve a purpopse? Resolved with 1105.
314 Impedance variation for transformers...
323 – transformer model connections are inconsistent with other classes (resolved?)
(Current transformer model)
365 - DAF/GDA/CIMXML ResourceID – Moved from Resolved to closed. No
change
373 - Domain.Float – Moved from Resolved to Closed. No change.
374 – Season does not inherit from Naming. Moved from Resolved to Closed.
No change.
377 – Inheritance on Quality61850 from IdentifiedObject. Change was made
previously, but never closed.
378 - ClearanceTag authorityName and workDescription changed to string.
Change was made previously, but never closed.
379 - GeneratingUnit.GrossToNetActivePowerCurve. Changed to plural.
Change was made previously, but never closed.
389 - Remaining data type issues. Change was made previously, but never
closed.
394 ...structured values...
395 Multiple regulation schedules at controlled point
396 Location of two winding transformer impedances
398 - AnalogValues shall be maintained if present. No change necessary.
400 – Reuse of common CIM classes. Moved from Ready to Close. No changes.
607 – Removed Load, CustomerLoad, and InductionMotorLoad.
608 – InductionMotorLoad documentation. Closed with 607.
615 - In association PSRType<->PowerSystemResource, add 's' to role
PowerSystemResource. Changed as suggested.
617 - In association CurveSchedule<->CurveScheduleDatas, rename roles to
Curve<->CurveDatas. Changed as suggested.
625 - simple rename to upper case FossilSteamSupply auxPowerversesVoltage
626 - In association Drives_SynchronousMachines<->DrivenBy_PrimeMover,
add 's' to role DrivenBy_PrimeMover. Changed as suggested.
628 - In class GeneratorControlSource, correct enumeration names. Changed as
suggested.
629 - In class GeneratorControlMode, correct enumeration names. Changed as
suggested.
630 In attribute HydroPowerPlant.plantRatedHead: float
631 In attribute Reservoir.spillwayCrestLength: float
632 – In association FuelAllocationSchedule<->FossilFuel, add 's' to role
FuelAllocationSchedule. Changed a suggested.
633 – In association HydroGeneratingUnit<->TailbayLossCurve, add 's' to role
TailbayLossCurve. Changed as suggested.
634 – In association GenSourcePumpDischarge<->UpstreamFrom, add 's' to role
UpstreamFrom. Changed as suggested.
635 -In association Reservoir<->InflowForecast, add 's' to role InflowForecast.
Changed as suggested.
636 – In association Reservoir<->LevelVsVolumeCurve, add 's' to role
LevelVsVolumeCurve. Changed as suggested.
637 - In association SpillsInto<->SpillsFrom, add 's' to role SpillsInto. Changed
as suggested.
642 - In association Measurements<->ValueAliasSet, rename role. Changed as
suggested.
648 - In association PSR<->OutageSchedule, rename role PSR to
PowerSystemResource. Changed as suggested.
649 - In association Breaker<->RecloseSequences, rename role Breaker to
ProtectedSwitch. Changed as suggested.
651 - In association InitiallyUsedBySynchronousMachine<-
>InitialReactiveCapabilityCurve, add 's' to role. Changed as suggested.
656 - association Operates_PSRs<->OperatedBy_Companies. Closed with 1105.
657 - In association Drives_SynchronousMachines<->DrivenBy_PrimeMover,
rename roles to SynchronousMachines<->PrimeMovers. Changed as suggested.
658 - In association Drives_AirCompressor<->DrivenBy_CombustionTurbine,
rename roles. Changed as suggested.
659 - In association Contain_AirCompressor<->MemberOf_CAESPlant, rename
roles. Changed as suggested.
660 - In association Contain_ThermalGeneratingUnit<->MemberOf_CAESPlant,
rename roles. Changed as suggested.
661 - In association Contain_ThermalGeneratingUnits<-
>MemberOf_CogenerationPlant, rename roles. Changed as suggested.
662 - In association Contain_ThermalGeneratingUnits<-
>MemberOf_CombinedCyclePlant, rename roles. Changed as suggested.
663 - In association Contains_SynchronousMachines<-
>MemberOf_GeneratingUnit, rename roles. Changed as suggested.
664 - In association Contain_HydroGeneratingUnits<-
>MemberOf_HydroPowerPlant, rename roles. Changed as suggested.
665 - In association Contain_HydroPumps<->MemberOf_HydroPowerPlant,
rename roles. Changed as suggested.
666 - In association Drives_HydroPump<->DrivenBy_SynchronousMachine,
rename roles. Changed as suggested.
667 - In association Controls<->ControlledBy_RegulatingCondEq, rename role.
Changed as suggested.
668 - In association Contains_Measurements<->MemberOf_PSR, rename roles.
Changed as suggested.
669 - In association (Accumulator) Contain_MeasurementValues<-
>MemberOf_Measurement, rename roles. Changed as suggested.
670 - In association (Analog) Contain_MeasurementValues<-
>MemberOf_Measurement, rename roles. Changed as suggested.
671 - In association (Analog) ControlledBy_Control<-
>MeasuredBy_Measurement, rename roles. Changed as suggested.
672 - In association (Discrete) ControlledBy_Control<-
>MeasuredBy_Measurement, rename roles. Changed as suggested.
673 - In association (Discrete) Contain_MeasurementValues<-
>MemberOf_Measurement, rename roles. Changed as suggested.
674 - In association (StringMeasurement) Contain_MeasurementValues<-
>MemberOf_Measurement, rename roles. Changed as suggested.
675 - In association Operates_Breakers<->OperatedBy_ProtectionEquipments,
rename roles. Changed as suggested.
676 - In association Contain_RemoteUnits<->MemberOf_CommunicationLinks,
rename roles. Changed as suggested.
677 - In association MemberOf_RemoteUnit<->Contains_RemotePoints, rename
roles. Changed as suggested.
678 - In association MemberOf_EquipmentContainer<->ConnectivityNodes,
rename role. Changed as suggested.
679 - In association MemberOf_Substation<->Contains_Bays, rename roles.
Changed as suggested.
680 - In association Contains_Bays<->MemberOf_VoltageLevel, rename roles.
Changed as suggested.
681 - In association Contains_Equipments<->MemberOf_EquipmentContainer,
rename roles. Changed as suggested.
682 - In association MemberOf_Substation<->Contains_CompositeSwitches,
rename roles. Association was removed previously.
683 – In association Contains_VoltageLevels<->MemberOf_Substation, rename
roles. Changed as suggested.
684 - In association MemberOf_PowerTransformer<-
>Contains_TransformerWindings, rename roles. Changed as suggested.
700 – attribute rename from amp to current Fuse.ampRating
721 – Ratings from Equipment Details. Moved from Ready to Close.
728 – cim for planning, transformer test data
730 – cim for planning, transformer impedance correction tables as function of
tap
731 – cim for planning – voltage and phase tap on same winding not possible in
model
735 – ERCOT contingencies.
745 – PowerTransformer recursive relationship
759 - ERCOT tap schedule
762 - BranchGroup – need to remove duplicates
766 – ERCOT tap ratio as function of tap position (TapRatioCurve)
786 – Equivalents renames of associations
810 – no class type in incremental file, just look up by MRID in reverse
difference
812 – 301 document does not contain some items in model
845 - Diagram arrow heads displayed on bidirectional associations in EA
870 – CIM/XML incremental pre-conditions not well defined
901 – Removed class MeasurementType and replaced with a string attribute on
class Measurement
906 – Regulation cannot use DayType for different day of week schedules.
915 – Move Assets classes to Meas, Protection, and Wires
916 – Move ConductorType, WireArrangement, and WireType to AssetsLinear.
917- WindingTest – No change
1014 – Remove transfCoolingType and HeatExchanger.
1053 – Add injections to equivalent model
1056 – Conforming induction motor load is not possible and other model restrictions.
1057 – UCTE Stable CIM version – clear roadmap for CIM development
1058 – UCTE Describe CIM object attributes - Harmonization of profiles
1059 UCTE – Delta transformer (no assumed center node) representation
1060 UCTE – Transformer regulation improvements
1061 – UCTE equivalent elements need to be distinquished in the model
1063 – UCTE Genetator. Moved from Ready to Close.
1064 – UCTE voltage limits + need VoltageLevel to TopologicalNode association
1071 – Remove UML tags root/leaf. Moved from Ready to Close.
1083 - EquivalentSource renamed without changes tracked in this file
1085 - Class/attribute dissapeared without changes tracked in this file -
replacement not clear.