本文主要讲述的是110VK配电系统(变电站)继电保护的配置,整定计算。目前,110KV变电站主要是直接向广大用户供应和分配电能,是包括发电、输变电和配电在内的整个电力系统的最终环节。由于电力系统具有发、供、用同时的特点,一旦配电系统发生故障,将造成系统对用户供电的中断,同时也有可能使整个电力系统受到影响,甚至被破坏,造成巨大的经济损失。因此,必须提高110KV配电系统的可靠性,给变电站的设备装设动作可靠、迅速、性能完善的保护,把故障影响限制在最小范围内, 保证向用户提供持续的电能。
资源推荐
资源详情
资源评论
目 录
摘要
概述
第一章 系统保护配置..................................................................................6
第一节 综述........................................................6
第二节 降压变压器 2B1、2B2 保护配置.....................................................7
第三节 35KV 线路保护配置..........................................................................7
第四节 10KV 线路保护配置........................................................................9*
第二章 短路电流计算....................................................................................10
第一节、网络参数计算..........................................................................10
第二节、短路电流计算..........................................................................10
第三章 降压变压器 2B1、2B2 的保护整定计算.........................................15
第一节 纵差动保护整定计算................................................................
第二节 复合电压起动过电流保护........................................................
第三节 变压器过负荷保护整定计算....................................................
第四章 35KV 线路保护整定计算..................................................................19
第五章 10KV 线路保护整定计算..................................................................23
第六章 短路电流计算等值阻抗图..............................................................34
附录:图一、系统保护配置图......................................................................37
图二、降压变压器 2B1、2B2 保护二次回路图................................38
图二、电气主接线图...........................................................................
表一、降压变压器 2B1、2B2 保护的动作值....................................39
表二、L31、L32、L33 线路的整定动作值......................................39
表三、L101、L105、L106、L1010 线路的整定动作值..................39
参考文献...............................................................................................40
摘要
本文主要讲述的是 配电系统(变电站)继电保护的配置,整定计算。
目前, 变电站主要是直接向广大用户供应和分配电能,是包括发电、输
变电和配电在内的整个电力系统的最终环节。由于电力系统具有发、供、用同
时的特点,一旦配电系统发生故障,将造成系统对用户供电的中断,同时也有
可能使整个电力系统受到影响,甚至被破坏造成巨大的经济损失。因此,必须
提高 配电系统的可靠性,给变电站的设备装设动作可靠、迅速、性能完
善的保护,把故障影响限制在最小范围内, 保证向用户提供持续的电能。
电力系统继电保护和安全自动装置是电力系统的重要组成部分。它对电力
系统安全稳定地运行和对用户的不间断供电起着极为重要的作用,没有继电保
护的电力系统是不能运行的。电力系统继电保护的设计与配置是否合理直接影
响到电力系统的安全稳定运行。如果设计与配置不当,继电保护将不能正确动
作,从而会扩大事故的停电范围。给国民经济带来严重的恶果,有时还可能造
成人身和设备安全事故。因此,为了保证 变电站的正常运行,必须根据
《规程》来设置变电站所需要的保护装置,并根据满足选择性、速动性、灵敏
性、可靠性进行整定值,使整个系统的各种继电保护有机协调地布置,正确地
发挥作用。
关键词:配电系统、变电站、电力系统继电保护
Summary
What this text mainly told is system (transformer substation ) disposition of relay
protection of 110VK distribution, calculate whole definitely. At present, 110KV
transformer substation to supply the masses of users with and assign the electric
energy directly mainly, it is the final links of the whole power system including
generate electricity , the power transmission and transformation and distribution.
Because the power system takes place, supports, uses the characteristic at the same
time , once the distribution system breaks down, the ones that cause the system to
supply power to users break down, may make the whole power system influenced at
the same time , even destroyed, cause the enormous economic losses. So must
improve 110KV distribution dependability of system, apparatus to give transformer
substation install movement reliable , rapidly , complete protection of performance,
influence the trouble to confine to minimum range, guarantee to offer the lasting
electric energy to users.
The relay protection of power system and security automatics are important
components of the power system. It operates and plays an extremely important role
safly in users' incessant power supply steadily in the power system, the power system
without relay protection can not run . The peace and steadiness that design and
disposition of relay protection of power system influence the power system directly
rationally runs . It design and it is the improper since it dispose,relay protection can
movements correct,it thus not will expand by power cut range of accident. Bring the
serious evil consequence to national economy, may also cause the apparatus incident
of personal sum sometimes. So for guarantee 110KV normal running of transformer
substation , must follow " rules " come , set up protector transformer substation need,
and moving , sensitivity , dependability carry on whole definite value according to the
alternative of meeting, rapidly, make various relay protection of the whole system fix
up organically coordinating , function correctly.
Keyword: Distribution system , transformer substation , power system relay
protection
概述
一、电力系统规划的概述
电力系统规划、设计及运行的根本任务是,在国民经济发展计划的统筹安
排下,合理开发、利用动力资源,用较少的投资和运行成本,来满足国民经各
部门及人民生活不断增长的需要,提供充足、可靠和质量合格的电能。
二、本变电所在电力系统中的地位和作用
桂平市电力供应十分紧张,特别是进入改善 9 月份以来,我市电力缺口高
达 70%以上,限电拉闸不能避免,确保电网的安全运行和有力缓解因限电拉闸
引发的社会各方面压力,建设一抽水蓄能水电站已成为当务之急,以改善桂平
的电网结构方式。
三、变电站负荷情况及所址概况
电压等级为三级 容量为 变电站。 侧
有两个电源,其中一个是水电厂 ,通过 线路与变电站连接,水电
厂除近区有少数负荷,所发电能大部分向该站输送,水电厂最大和最小运行方
式归算到 母线阻抗分别是 欧、 欧;另一个是系统 ,系
统 归 算 到 母 线 阻 抗 是 欧 。 侧 是 单 母 线 , 由 线 路
、
、
组成环网对变电站 、 供电,该网正常情况是闭环
运行, 侧是单母线分段,共有 回出线。有关接线图和参数在附录中有
说明。
.本站经 回 线路与系统相连,分别用 和 向本地用户
供电。
任务: 变压器继电保护。
变电所地址的气候属于广西正常情况查资料,广西年平均气温 ~
,夏季平均气温 ~,最高气温 ;雷暴日大于 天年。
系统参数: 系统为无穷大系统,距离本站 ,线路阻抗按
欧 计算。
站用电为 。 根据本站为 回 线路进线,、
最大负荷时间分别为 、,可以判断本站为重要变电站,在进行设
计时,应该侧重于供电的可靠性和灵活性。
四、系统对本变电所的技术要求
!主变容量: ";
!电压等级:;
!主变型式:
三 相 三 绕 组 有 载 调 压 电 力 变 压 器 , 有 载 调 压 范 围 : 高 压
110±8×1.25%KV,中压 38.5±2×2.5%KV,低压 6.3 、6.6 、10.5 、11 KV;
三相双绕组有载调压电力变压器,有载调压范围:#"$
。
!进出线圈路数:进线 侧 回,进线 侧 回出线
侧 回进线 侧 回出线 侧 回;
!主变中性点直接接地。
第一章 电气主接线的设计
电气主接线是由各种电气设备及其接线组成,用以接收和分配电能,是供电
系统的重要组成部分。它与电源的回路数,电压等级和负荷的大小、级别以及所
用变压器的台数、容量等因素有关。确定变电所的主接线对变电所电器设备的选
择,配电装置的布置及运行的可靠性与经济性等都有密切的关系,主接线设计是
变电所设计中的重要任务之一。
第一节 电气主接线设计原则
电气主接线设计时,所遵循的原则:符合设计任务书的要求,符合有关的方
针,政策和技术规范,规程;结合具体工程特点,设计出技术经济合理的主接线。
根据以上原则于任务书本设计主接线方案应达到以下要求: